Electrical 10 min read Feb 10, 2026

How to Size Wire for Long Runs

Why voltage drop matters more than ampacity once you get past 100 feet

Most electricians size wire based on ampacity tables and stop. That works fine for short runs. A 6 AWG copper wire is rated for 65 amps at 75°C, so you use it for a 60-amp circuit and move on. But once you get past 100 feet, ampacity stops being the limiting factor. Voltage drop takes over.

Voltage drop is the loss of voltage between the source and the load due to resistance in the wire. A 60-amp load 200 feet away can easily see 8-10 volts of drop on a 6 AWG circuit. That's 3-4% at 240V, which is technically within NEC limits (5% total for feeders and branch circuits combined). But many motors, electronics, and LED drivers perform poorly below 95% of rated voltage. The equipment might work, but it won't work well.

Voltage Drop vs Ampacity: Two Different Problems

Ampacity is about safety. It's the maximum current a wire can carry without overheating and damaging the insulation. The NEC provides ampacity tables in Article 310 based on conductor size, insulation type, and ambient temperature. If you exceed the ampacity, the wire gets hot, insulation degrades, and you risk a fire. This is a hard limit.

Voltage drop is about performance. It's the loss of voltage between the panel and the load due to the resistance of the wire. Voltage drop doesn't cause fires, but it causes motors to overheat, lights to dim, and electronics to malfunction. The NEC allows up to 5% total drop (3% for feeders, 2% for branch circuits), but that's a recommendation, not a code requirement. Many engineers design for 2-3% total drop to avoid performance problems.

On short runs (under 50 feet), ampacity is almost always the binding constraint. The wire size needed to carry the current safely is larger than the wire size needed to keep voltage drop under 3%. But once you get past 100 feet, voltage drop starts to dominate. A 60-amp circuit might need 4 AWG or even 2 AWG to stay under 3% drop at 200 feet, even though 6 AWG is rated for 65 amps.

This is the key insight: ampacity and voltage drop are independent constraints. You have to check both, and you have to use the larger wire that satisfies the tighter constraint. For long runs, that's almost always voltage drop.

NEC Article 210.19(A)(1) and 215.2(A)(1) recommend limiting voltage drop to 5% total, with 3% for feeders and 2% for branch circuits. But "recommend" is not "require." Inspectors rarely fail installations for voltage drop unless it causes code violations elsewhere (like motor overload).

The Voltage Drop Formula

The voltage drop formula for single-phase circuits is: VD = (2 × K × I × D) / CM, where K is the resistivity constant, I is the current in amps, D is the one-way distance in feet, and CM is the circular mil area of the conductor. The factor of 2 accounts for the round trip: current flows out on the hot wire and back on the neutral.

The resistivity constant K depends on the conductor material and temperature. For copper at 75°C, K = 12.9. For aluminum at 75°C, K = 21.2. These are the values you use for most residential and commercial work because 75°C is the standard rating for THHN/THWN wire.

Circular mils (CM) is an odd unit, but it's what the formula uses. For standard wire sizes, you can look up CM in NEC Chapter 9, Table 8. For example, 10 AWG is 10,380 CM, 6 AWG is 26,240 CM, 2 AWG is 66,360 CM. Bigger wire = more CM = less resistance = less voltage drop.

Let's work an example. You have a 50-amp load at 240V, 200 feet away. You're using 6 AWG copper (26,240 CM). VD = (2 × 12.9 × 50 × 200) / 26,240 = 9.8 volts. That's 4.1% drop at 240V. If your target is 3%, you need to go up to 4 AWG (41,740 CM), which drops VD to 6.2 volts (2.6%).

Formula: Voltage drop (single-phase):
VD = (2 × K × I × D) / CM

Voltage drop (three-phase):
VD = (1.732 × K × I × D) / CM

K = 12.9 (copper, 75°C)
K = 21.2 (aluminum, 75°C)
I = current (amps)
D = one-way distance (feet)
CM = circular mil area (from NEC Chapter 9, Table 8)
Electrical

Wire Sizing Calculator

Find the right AWG wire gauge for any electrical run. Enter amps, distance, and voltage to get NEC-compliant sizing with derating, voltage drop, and copper vs aluminum cost comparison.

Launch Calculator →

NEC Derating: The Part Most People Skip

Ampacity tables in NEC 310.16 assume three conditions: conductors are in free air or in a raceway with no more than three current-carrying conductors, ambient temperature is 30°C (86°F), and the conductor insulation is rated for 75°C. If any of these conditions change, you have to derate the ampacity.

Temperature correction is in NEC 310.15(B)(2)(a). If the ambient temperature is higher than 30°C, you multiply the ampacity by a correction factor. For example, at 40°C (104°F), the correction factor for 75°C wire is 0.88. A 6 AWG conductor rated for 65 amps at 30°C is only good for 57 amps at 40°C. Attics in summer can hit 50°C (122°F), where the correction factor drops to 0.75. Your 65-amp wire is now a 49-amp wire.

Conduit fill adjustment is in NEC 310.15(B)(3)(a). If you have more than three current-carrying conductors in a raceway, you multiply the ampacity by an adjustment factor. For 4-6 conductors, the factor is 0.8. For 7-9 conductors, it's 0.7. This is where multi-circuit conduit runs get tricky.

The two derating factors multiply. A 6 AWG conductor in a 40°C attic with four conductors in the conduit is derated to 65 × 0.88 × 0.8 = 46 amps. If your load is 50 amps, 6 AWG isn't enough. You need 4 AWG, which gives you 85 × 0.88 × 0.8 = 60 amps after derating.

Warning: Common mistake: Using ampacity tables directly without checking temperature and conduit fill. This is the most frequent reason DIY installations fail inspection. Always apply correction factors before comparing ampacity to load.

Copper vs Aluminum: A Real-World Comparison

Aluminum is cheaper than copper by about 40% per foot for the same ampacity. But aluminum has higher resistance, so you need 1-2 wire sizes larger to get the same voltage drop. For long runs (100+ feet), the cost difference narrows, and for very long runs (300+ feet), aluminum often wins despite the larger size.

A 2 AWG copper wire costs about $2.50/foot and has an ampacity of 115 amps at 75°C. A 1/0 AWG aluminum wire costs about $1.80/foot and has an ampacity of 120 amps. For a 100-foot run, that's $250 for copper vs $180 for aluminum. The aluminum is 28% cheaper.

But aluminum has different termination requirements. You need anti-oxidant compound on the terminations to prevent corrosion. You need to use the correct torque (aluminum is softer than copper, so over-tightening deforms the conductor). And you need to verify that your breakers, panels, and equipment are rated for aluminum conductors. Many residential panels are marked "CU/AL" (copper or aluminum), but some are copper-only.

The practical rule: for feeders and service entrances longer than 100 feet, aluminum is worth considering. For branch circuits, copper is usually easier unless you're doing a large commercial job. For short runs under 50 feet, copper is the default.

Common Mistakes on Long Runs

The most common mistake is sizing wire based on ampacity alone without checking voltage drop. This works fine for short runs but fails on long runs. A 10 AWG wire is rated for 35 amps, which is fine for a 30-amp circuit. But if that circuit is 150 feet away, you're looking at 7-8% voltage drop. The equipment might work, but motors will run hot and lights will dim.

The second mistake is using indoor-rated wire outdoors. THHN is rated for dry or damp locations. THWN is rated for wet locations. If you run a feeder to a detached garage or barn, you need THWN or direct-burial cable (UF). Using THHN in conduit exposed to rain is a code violation.

The third mistake is undersizing the neutral. For single-phase loads, the neutral carries the same current as the hot, so it needs to be the same size. For three-phase balanced loads, the neutral carries little to no current. But for three-phase loads with significant single-phase components, the neutral can carry close to the full phase current.

The fourth mistake is not accounting for future loads. If you're running a feeder to a barn and you size it for the current load, you'll regret it when you want to add a compressor or a heater. The incremental cost of going from 6 AWG to 4 AWG on a 200-foot run is maybe $150. The cost of pulling new wire later is $2,000+.

The fifth mistake is not applying the NEC 125% rule for continuous loads. A load is continuous if it runs for 3 hours or more. HVAC, well pumps, and some lighting qualify. For continuous loads, you have to size the wire and breaker for 125% of the load.

Tip: When in doubt, go one size larger. The cost difference between 6 AWG and 4 AWG is small compared to the cost of pulling new wire later. Undersized wire is a permanent headache. Oversized wire is cheap insurance.

Frequently Asked Questions

3% or less for critical loads (motors, electronics, LED lighting). 5% is acceptable for resistive loads (heaters, incandescent lights). The NEC recommends 3% for feeders and 2% for branch circuits, totaling 5%. Many engineers target 2-3% total to avoid performance issues.
It matters more for 120V. A 5-volt drop is 4.2% at 120V but only 2.1% at 240V. This is why long 120V runs are harder to size. If you have a choice, use 240V for long-distance loads.
The circuit will probably pass inspection (voltage drop is a recommendation, not a requirement in most cases), but the equipment will underperform. Motors will draw more current to compensate, which makes them run hot and shortens their life. LEDs will dim or flicker. You won't have a fire, but you'll have annoyed users and early equipment failures.
Yes, but only in a junction box with proper connectors. Splices are not allowed in walls or conduit unless the junction box is accessible. For long runs, splicing adds cost and labor without saving much, so it's usually better to pull a longer wire.
Disclaimer: This guide provides general principles for wire sizing on long runs. Actual installations must comply with the National Electrical Code (NEC) and local amendments. Always consult a licensed electrician for final design and installation. Improper wire sizing can result in code violations, equipment damage, and fire hazards.

Calculators Referenced in This Guide

Electrical Live

Can I Run This On That?

Check if your circuit breaker and wiring can handle a specific appliance. Enter breaker size, wire gauge, and load wattage for a pass/fail verdict based on NEC standards.

Electrical Live

Wire Sizing Calculator

Find the right AWG wire gauge for any electrical run. Enter amps, distance, and voltage to get NEC-compliant sizing with derating, voltage drop, and copper vs aluminum cost comparison.

Electrical Live

Panel Load Study

Do you actually need a panel upgrade? Walk your breaker panel with NEC Article 220 demand factors. See connected load vs. calculated demand and test whether an EV charger, heat pump, or hot tub fits.

Related Guides

Electrical 12 min

Wiring a Detached Shop or Garage

How to plan electrical service for a detached shop, garage, or outbuilding. Load lists, subpanel sizing, feeder wire, voltage drop on long runs, and NEC burial requirements.