Skip to main content
Shops & Outbuildings 9 min read Feb 11, 2026

Why Your Outbuilding Motor Won't Start

Voltage drop over long wire runs is the silent killer of motors in barns, shops, and outbuildings

The motor on your shop air compressor hums, struggles, and trips the breaker. The welder in the barn barely strikes an arc. The grain dryer fan in the outbuilding runs slow and hot. You replace the motor, and the new one does the same thing. You call an electrician, and he says the motor is fine. The problem is not the motor. The problem is 200 feet of undersized wire between the main panel and the outbuilding.

Voltage drop is the loss of electrical pressure that occurs when current flows through wire over distance. Every foot of wire has resistance, and that resistance converts some of the voltage into waste heat instead of delivering it to the motor. The longer the wire run and the smaller the wire gauge, the more voltage you lose. A motor that needs 240 volts to start might only be getting 210 volts at the end of a long run, and that 12% drop is enough to prevent the motor from developing starting torque. This guide explains why it happens, how to calculate it, and what to do about it.

What Voltage Drop Actually Does to a Motor

An induction motor produces torque in proportion to the square of the applied voltage. If voltage drops by 10%, torque drops by roughly 19%. If voltage drops by 15%, torque drops by roughly 28%. Starting torque, which is the torque the motor produces to get the shaft turning from a dead stop, is already the hardest demand on the electrical system. A motor that needs 100% starting torque at 240 volts can only produce 81% at 216 volts. If the connected load (compressor, saw, grinder) requires more than 81% of rated starting torque, the motor stalls.

A stalled motor is not just an inconvenience. It draws locked-rotor current, which is 5 to 7 times the normal running current, and it draws that current continuously instead of for the brief 1 to 2 second starting interval. The wire run that was already dropping voltage under normal load now drops even more under locked-rotor current, creating a feedback loop: low voltage causes a stall, the stall draws more current, more current causes more voltage drop, and the voltage drops further. The thermal overload or breaker eventually trips, but not before the motor windings get hot.

Repeated stalling and overheating is the primary cause of premature motor failure in outbuildings. The motor is not defective. The wire feeding it is too small for the distance. Replacing the motor without fixing the voltage drop guarantees the new motor will fail the same way.

The NEC (National Electrical Code) recommends a maximum of 3% voltage drop for branch circuits and 5% total from the service entrance to the final outlet. For a 240-volt circuit, 5% is 12 volts, meaning the motor should see at least 228 volts. Many outbuilding installations violate this guideline because the wire was sized for current capacity (ampacity) without accounting for the distance. A 10-gauge wire is rated for 30 amps, which is plenty for a 5 HP motor. But at 200 feet, the voltage drop at full load is over 7%, well past the point where motors struggle.

Warning: Voltage and torque: Motor torque varies with the square of voltage. A 10% voltage drop cuts available torque by 19%. A 15% drop cuts it by 28%. If the motor can't develop enough torque to overcome the load, it stalls and draws locked-rotor current until the breaker trips. This is the number one motor killer in outbuildings.
Shops & Outbuildings

Long-Run Voltage Drop Calculator

Calculate voltage drop for long wire runs to detached shops, barns, garages, and outbuildings. Compares copper vs aluminum, shows motor starting voltage impact, and recommends the right wire size for your distance and load.

Launch Calculator →

How to Calculate Voltage Drop for Your Wire Run

The voltage drop formula for single-phase circuits is: Vd = (2 × L × I × R) / 1000, where Vd is the voltage drop in volts, L is the one-way distance in feet, I is the current in amps, and R is the wire resistance in ohms per 1000 feet. For copper wire, common resistance values are: 14 AWG = 3.14 Ω/1000ft, 12 AWG = 1.98, 10 AWG = 1.24, 8 AWG = 0.778, 6 AWG = 0.491, 4 AWG = 0.308, 2 AWG = 0.194, 1/0 AWG = 0.122.

Example: A 5 HP single-phase motor draws about 28 amps at full load on a 240-volt circuit. The outbuilding is 200 feet from the main panel. Using 10 AWG copper wire: Vd = (2 × 200 × 28 × 1.24) / 1000 = 13.9 volts. That is a 5.8% drop, leaving only 226 volts at the motor. During startup, the motor draws 140 to 196 amps (5-7 times full load), and the momentary voltage drop is catastrophic: (2 × 200 × 168 × 1.24) / 1000 = 83 volts dropped, leaving only 157 volts at the motor. The motor cannot start.

To keep the drop under 3% at full load current for the same 200-foot run: you need Vd ≤ 7.2 volts. Working backward: R ≤ (7.2 × 1000) / (2 × 200 × 28) = 0.643 Ω/1000ft. That requires 6 AWG wire (0.491 Ω/1000ft). Jumping from 10 AWG to 6 AWG costs more in wire, but it is the only fix that actually solves the problem.

For three-phase circuits, the formula changes to: Vd = (1.732 × L × I × R) / 1000. Three-phase has a natural advantage because the current per conductor is lower for the same horsepower, and the multiplier is 1.732 instead of 2. A 5 HP three-phase motor draws about 15 amps at 240 volts, less than half the single-phase current. This is why electricians recommend three-phase power for outbuildings with significant motor loads whenever it is available.

Formula: Single-phase voltage drop:
Vd = (2 × L × I × R) / 1000

L = one-way distance (feet)
I = current (amps)
R = wire resistance (Ω/1000 ft)

% drop = (Vd / source voltage) × 100
Keep below 3% for branch circuits, 5% total.
Shops & Outbuildings

Long-Run Voltage Drop Calculator

Calculate voltage drop for long wire runs to detached shops, barns, garages, and outbuildings. Compares copper vs aluminum, shows motor starting voltage impact, and recommends the right wire size for your distance and load.

Launch Calculator →

Sizing Wire for Distance: The Fix That Actually Works

The solution to voltage drop is straightforward: use larger wire. The wire size that meets ampacity requirements (current-carrying capacity based on insulation temperature rating) is a minimum, not a recommendation. For outbuilding runs over 100 feet, you almost always need to go up one or two wire sizes beyond the ampacity minimum to keep voltage drop within acceptable limits.

A practical sizing table for single-phase 240V circuits to outbuildings at 3% maximum drop: a 20-amp circuit at 100 feet needs 10 AWG (ampacity minimum); at 200 feet it needs 6 AWG; at 300 feet it needs 4 AWG. A 30-amp circuit at 100 feet needs 8 AWG; at 200 feet it needs 4 AWG; at 300 feet it needs 2 AWG. A 50-amp circuit at 100 feet needs 6 AWG; at 200 feet it needs 2 AWG; at 300 feet it needs 1/0 AWG.

Aluminum wire is a cost-effective alternative for long runs. Aluminum costs about 40% less per foot than copper for the same ampacity, and the weight savings make it easier to pull through conduit. The tradeoff is that aluminum has higher resistance per foot, so you need to go up one size compared to copper (for example, 4 AWG aluminum instead of 6 AWG copper). Aluminum also requires anti-oxidant compound at every connection and compatible lugs rated for aluminum. Done correctly, aluminum feeders are the standard choice for outbuilding runs of 100 feet or more.

If the outbuilding already has undersized wire in conduit, you may be able to pull new wire without trenching. If the existing conduit is large enough for the new wire (check conduit fill calculations), you can pull the old wire out and pull the new wire in. If the conduit is too small, you need a new conduit run or direct-burial cable. Direct-burial UF cable is allowed for underground runs but must be buried at least 24 inches deep (12 inches if in rigid conduit). The trenching cost is typically $3 to $8 per linear foot, which is often the largest expense in an outbuilding electrical upgrade.

Tip: Aluminum saves money on long runs. For outbuilding feeders over 100 feet, aluminum wire is typically the better value. It costs 40% less than copper and is lighter to handle. Go up one wire size versus copper (e.g., 4 AWG aluminum = 6 AWG copper ampacity). Use anti-oxidant compound and AL-rated lugs at every connection.
Electrical

Wire Sizing Calculator

Find the right AWG wire gauge for any electrical run. Enter amps, distance, and voltage to get NEC-compliant sizing with derating, voltage drop, and copper vs aluminum cost comparison.

Launch Calculator →

Symptoms: How to Tell If Voltage Drop Is Your Problem

Not every motor problem is voltage drop, but certain symptoms are strong indicators. The motor hums loudly but turns slowly or does not turn at all when started under load. The motor starts fine when unloaded (no belt, no compressor head) but stalls under load. Lights in the outbuilding dim noticeably when the motor starts. The breaker trips after 5 to 15 seconds, which is the thermal overload time for locked-rotor current. The motor runs but is noticeably hot to the touch after even short operation.

To confirm voltage drop, measure voltage at the motor terminals while the motor is running at full load. Compare this to the voltage at the main panel. If the difference is more than 5% of the panel voltage, voltage drop is the problem. For example, if the panel reads 243 volts and the motor terminals read 224 volts, the drop is 19 volts, or 7.8%. That is enough to cause problems with starting torque and motor overheating.

A common misdiagnosis is a bad capacitor. Start capacitors boost starting torque on single-phase motors, and a weak or failed capacitor produces symptoms similar to voltage drop: slow starting, humming, and tripping. The difference is that a capacitor problem shows up even with good voltage at the motor terminals. If you measure 235+ volts at the motor and it still will not start, check the capacitor. If you measure 215 volts or less, the wire is the problem regardless of capacitor condition.

Another misdiagnosis is a weak breaker. Some electricians will upsize the breaker when a motor trips repeatedly. This is dangerous. The breaker is sized to protect the wire, not the motor. If the motor is stalling due to voltage drop and drawing locked-rotor current, a larger breaker allows that current to flow longer, overheating the wire and creating a fire hazard. The correct fix is always larger wire, never a larger breaker on the same wire.

Warning: Never upsize the breaker to fix a starting problem. The breaker protects the wire from overheating. If the motor stalls and draws locked-rotor current, a larger breaker lets that current flow longer, overheating the wire. The correct fix is larger wire, not a larger breaker. Upsizing the breaker on undersized wire creates a fire hazard.

Other Solutions: Soft Starters, Phase Converters, and Subpanels

If replacing the wire is impractical or too expensive, several alternatives can mitigate voltage drop problems. A soft starter reduces the inrush current during motor startup by ramping the voltage up gradually over 2 to 10 seconds. Instead of hitting the wire with 6 times full-load current instantaneously, the soft starter limits inrush to 2 to 3 times full-load current. The reduced inrush causes less voltage drop, and the motor accelerates smoothly instead of slamming into a stall. Soft starters cost $200 to $600 for motors up to 10 HP and are a practical retrofit when rewiring is not feasible.

A static phase converter generates a third phase from single-phase power, allowing the use of three-phase motors. Three-phase motors draw less current per leg than equivalent single-phase motors, which reduces voltage drop by 40 to 50 percent on the same wire. A 5 HP three-phase motor on a static phase converter draws about 15 amps per leg instead of 28 amps on single phase. The voltage drop on the same 200-foot, 10 AWG run drops from 5.8% to about 2.5%. The converter costs $400 to $800, and the three-phase motor may cost slightly more than a single-phase equivalent, but the total investment is often less than rewiring.

A subpanel at the outbuilding with its own feeder from the meter is another option if multiple circuits are needed. Instead of running separate circuits for each load, you run one properly sized feeder to a small panel in the outbuilding and branch from there. This concentrates the cost in one large wire run instead of multiple smaller ones. A 100-amp subpanel with a 200-foot feeder in 2 AWG aluminum costs about the same as running two separate 30-amp circuits in 6 AWG copper, but it gives you much more capacity and flexibility for future loads.

Tip: Soft starters are the cheapest fix for existing wire. A $300 soft starter reduces inrush current by 50–60%, which cuts the startup voltage drop proportionally. It does not fix the steady-state drop during running, but for motors that start fine and run hot, a soft starter can buy you time until rewiring is in the budget.

Frequently Asked Questions

For 3% maximum voltage drop at 240 volts and 20 amps full load, 10 AWG copper is good for about 115 feet one way. Beyond that, you need to upsize. At 200 feet, you need 6 AWG. At 300 feet, you need 4 AWG. These distances assume continuous load. If the load is intermittent, you have slightly more margin.
Never. Extension cords are not rated for continuous motor loads, and the voltage drop on a typical 12-gauge, 100-foot extension cord at 15 amps is over 5%. The cord overheats, the motor starves for voltage, and both are fire hazards. If you need temporary power to an outbuilding motor, use a properly sized portable cable rated for the current and distance.
Yes. The voltage dropped across the wire is converted to heat in the wire itself. At 5% voltage drop carrying 30 amps, the wire dissipates about 360 watts as heat. That is $250 to $400 per year in wasted electricity at typical rates, in addition to the motor performance problems. Fixing voltage drop saves energy and protects equipment.
240V is better for voltage drop because the current is lower for the same wattage (P = V × I). A 5 HP motor on 240V draws 28 amps; the same motor on 120V would draw 56 amps, doubling the voltage drop. This is why 240V circuits are standard for outbuilding motor loads. 208V (from three-phase wye systems) works fine but provides slightly less torque margin than 240V.
Disclaimer: This guide is for educational purposes only. All electrical work must comply with the National Electrical Code (NEC) and local building codes. Wire sizing, breaker selection, and panel installations must be performed by or inspected by a licensed electrician. Working with electrical systems is dangerous and can cause fire, injury, or death if done incorrectly.

Calculators Referenced in This Guide

Electrical Live

Wire Sizing Calculator

Find the right AWG wire gauge for any electrical run. Enter amps, distance, and voltage to get NEC-compliant sizing with derating, voltage drop, and copper vs aluminum cost comparison.

Shops & Outbuildings Live

Long-Run Voltage Drop Calculator

Calculate voltage drop for long wire runs to detached shops, barns, garages, and outbuildings. Compares copper vs aluminum, shows motor starting voltage impact, and recommends the right wire size for your distance and load.

Related Guides

Electrical 10 min

How to Size Wire for Long Runs

Why voltage drop matters more than ampacity on long wire runs, how NEC derating works, copper vs aluminum tradeoffs, and the mistakes that fail inspection.

Shops & Outbuildings 9 min

Why Your Well Pump Trips the Breaker

Well pump breaker trips are usually caused by undersized wire, voltage drop on long runs, failing capacitors, or a pump drawing too many amps. How to diagnose the real problem before replacing the pump.