Skip to main content
Solar & Renewables Free Pro Features Available

Battery Bank Sizing Calculator — Capacity, Configuration & Autonomy

Size Lead-Acid and LiFePO4 Battery Banks for Off-Grid, Backup, and Hybrid Solar Systems

Free battery bank sizing calculator for solar installers, off-grid system designers, and electricians. Enter your daily energy consumption in kWh or Ah, select battery chemistry (flooded lead-acid, AGM, gel, or LiFePO4), set depth of discharge (DoD) and autonomy days, and the calculator determines the total bank capacity, number of batteries, and series/parallel configuration for your system voltage. Includes temperature derating for cold-climate installations, cycle life projections at your operating DoD, and estimated replacement cost per kWh stored over the bank's lifetime.

Pro Tip: The number one battery bank killer is chronic undercharging, not overdischarging. An undersized solar array that cannot fully recharge the bank by mid-afternoon leaves sulfation on lead-acid plates that accumulates irreversibly. Size your array to deliver at least 10-15% more daily energy than the bank needs for a full recharge, and ensure your charge controller can deliver the absorption-stage current the bank requires. For LiFePO4, undercharging is less damaging but still reduces usable capacity because the BMS may trigger low-voltage cutoff earlier as cell imbalance grows without regular full charges. A battery bank is only as good as the charging system behind it.

PREVIEW All Pro features are currently free for a limited time. No license key required.

Battery Bank Sizing Calculator

How It Works

  1. Enter Daily Energy Consumption

    Input your daily load in kWh or amp-hours at the battery bank voltage. For off-grid systems, use the highest-consumption day of the year. For backup systems, enter the critical-load consumption during an outage. Include inverter inefficiency (typically 5-10% overhead) in the load number because the battery must supply more energy than the AC loads consume.

  2. Select Battery Chemistry

    Choose flooded lead-acid (FLA), sealed AGM, sealed gel, or lithium iron phosphate (LiFePO4). Each chemistry has different DoD limits, cycle life curves, temperature sensitivity, and cost per kWh. FLA is cheapest upfront but requires maintenance and tolerates only 50% DoD. LiFePO4 costs 2-3x more upfront but handles 80-90% DoD and lasts 3-5x longer.

  3. Set Depth of Discharge and Autonomy Days

    Depth of discharge is the percentage of total capacity you plan to use daily. Lead-acid banks are typically limited to 50% DoD for acceptable cycle life. LiFePO4 banks routinely operate at 80% DoD. Autonomy days is the number of consecutive cloudy days the bank must sustain loads without solar recharging. Off-grid systems in cloudy climates typically require 3-5 days of autonomy.

  4. Configure System Voltage

    Select the battery bank voltage: 12V, 24V, or 48V. Higher voltage means lower current for the same power, which reduces wire size and losses. Systems over 2 kW typically use 24V or 48V. Large off-grid systems (5 kW+) almost always use 48V. The voltage must match your charge controller input and inverter DC input specifications.

  5. Review Bank Configuration

    The calculator outputs total bank capacity in Ah and kWh, number of batteries needed, series and parallel configuration, estimated cycle life at your operating DoD, temperature-derated capacity for your climate, and cost per kWh stored over the bank's projected lifetime. Use these numbers to compare chemistries and optimize the balance between upfront cost and long-term value.

Built For

  • Off-grid solar designers sizing battery banks to match array production and daily load for year-round self-sufficiency
  • Solar installers adding battery backup to grid-tied systems for essential-loads panels during utility outages
  • Electricians configuring series/parallel battery strings to achieve the correct voltage and capacity for inverter specifications
  • RV and marine electricians sizing house battery banks for boondocking with solar charging
  • Telecom engineers sizing backup battery banks for cell tower sites with 72-hour autonomy requirements
  • Homeowners comparing lead-acid versus lithium battery costs on a lifetime cost-per-kWh basis for off-grid cabins

Features & Capabilities

Multi-Chemistry Support

Covers flooded lead-acid, AGM, gel, and LiFePO4 with chemistry-specific defaults for maximum DoD, charge voltage setpoints, temperature compensation coefficients, self-discharge rates, and cycle life curves. Each chemistry behaves differently and the calculator applies the correct parameters automatically when you select the type.

Depth of Discharge Optimization

Shows cycle life projections at different DoD levels so you can find the economic sweet spot. A lead-acid battery cycled to 50% DoD may last 1,200 cycles, but the same battery at 30% DoD may last 2,500 cycles. The calculator computes cost-per-kWh-delivered over the bank's lifetime at your chosen DoD to identify the most economical operating point.

Temperature Derating

Battery capacity decreases in cold temperatures. A lead-acid battery at 32F (0C) delivers only about 80% of its rated capacity at 77F (25C). At 0F (-18C), capacity drops to roughly 60%. The calculator applies temperature correction factors based on your minimum expected operating temperature so the bank is sized for real-world conditions, not laboratory ratings.

Series/Parallel Configuration

Determines the exact number of batteries in series to achieve system voltage and the number of parallel strings to achieve total capacity. Displays the wiring configuration diagram notation (e.g., 4S2P = four in series, two parallel strings). Flags configurations that exceed recommended parallel string limits for the selected chemistry.

Autonomy Day Modeling

Calculates the total bank capacity needed to sustain loads through consecutive days without solar recharging. Accounts for the compounding effect of daily discharge without full recharge. For off-grid systems in the Pacific Northwest or northern latitudes, 3-5 autonomy days prevent generator dependence during extended overcast periods.

Lifetime Cost Analysis

Compares total cost of ownership across chemistries by factoring in cycle life, replacement frequency, and maintenance costs. LiFePO4 at $400/kWh with 5,000 cycles often costs less per kWh delivered than FLA at $150/kWh with 1,200 cycles. The calculator makes this comparison transparent so purchasing decisions are based on lifetime economics, not sticker price.

Frequently Asked Questions

It depends entirely on your daily consumption and autonomy requirement. A modest off-grid cabin using 5 kWh/day with 3 days of autonomy at 50% DoD needs 30 kWh of battery capacity, which is eight 6V 225Ah flooded golf cart batteries in a 48V configuration (8S1P). A full-size off-grid home using 20 kWh/day with 3 days of autonomy needs 120 kWh of capacity, which is a major battery installation regardless of chemistry. Start by accurately measuring your daily load, then let the calculator determine the bank size. Most people underestimate their consumption by 30-50% on the first pass.
The industry standard recommendation is 50% DoD for daily cycling in off-grid solar applications. This provides a reasonable balance between usable capacity and cycle life, typically delivering 1,000-1,500 cycles for quality flooded lead-acid batteries. Discharging to 80% DoD dramatically shortens life to 300-500 cycles. Limiting discharge to 30% DoD extends life to 2,500+ cycles but requires a much larger (and more expensive) bank. For emergency backup systems that cycle infrequently, 80% DoD is acceptable because calendar aging will likely end the battery before cycle aging does.
For daily-cycling applications like off-grid solar, LiFePO4 almost always wins on lifetime cost despite costing 2-3x more upfront. A LiFePO4 bank at 80% DoD delivers 3,000-5,000 cycles, while lead-acid at 50% DoD delivers 1,000-1,500 cycles. The lithium bank also provides 60% more usable capacity per dollar of installed capacity because of the deeper DoD. Additionally, LiFePO4 is maintenance-free, weighs 60% less, and has a flat discharge curve that delivers consistent voltage until nearly empty. The main scenario where lead-acid still makes sense is very low-cycle applications like seasonal cabins used 30-50 days per year, where calendar aging dominates and the cheaper upfront cost of lead-acid is advantageous.
Cold temperatures reduce electrochemical reaction rates, decreasing available capacity. For lead-acid batteries, the rule of thumb is a 1% capacity loss per degree Fahrenheit below 77F. At 32F, a 200Ah battery delivers approximately 160Ah (80%). At 0F, it delivers roughly 120Ah (60%). LiFePO4 batteries are less affected by cold on discharge but must not be charged below 32F without a heated BMS, as lithium plating on the anode causes permanent damage. If your batteries are in an unheated space, the calculator applies temperature derating to ensure the bank is large enough to deliver the required energy at your coldest expected temperature.
No. Never mix battery chemistries, capacities, ages, or brands in a bank. Batteries in a series string must be identical because the weakest cell limits the entire string. In parallel strings, a weaker battery draws charging current from stronger batteries, accelerating degradation of both. When one battery in a bank fails, the correct practice is to replace the entire bank or at minimum the entire parallel string. If budget forces a partial replacement, match the exact same model and try to match the age within 6 months. The most common cause of premature bank failure is mixing a new battery with old batteries that drag it down to their degraded performance level.
Disclaimer: This calculator provides battery bank sizing estimates for planning purposes. Actual battery performance depends on temperature, charge/discharge rates, maintenance practices, and manufacturer specifications. Battery installations involve electrical hazards including short-circuit risk, hydrogen gas generation (lead-acid), and thermal runaway (lithium). All battery work must comply with NEC Article 480 and local codes. Consult a qualified solar installer or electrical engineer for final system design. ToolGrit is not responsible for battery selection or installation outcomes.

Learn More

Solar & Renewables

Battery Bank Sizing for Off-Grid Solar

How to size a battery bank for off-grid solar. Covers lead-acid vs LiFePO4, depth of discharge, cycle life, temperature effects, series and parallel configuration, charge controller pairing, and maintenance.

Related Tools

Solar & Renewables Live

Solar Array Sizing Calculator

Size your solar panel array from daily kWh load, peak sun hours by region, system losses, and tilt derating. Grid-tied and off-grid modes with monthly production estimates.

Solar & Renewables Live

DC Wire Sizing Calculator

Calculate wire gauge and voltage drop for 12V, 24V, and 48V DC circuits. Solar PV, RV, marine, and automotive applications with NEC ampacity verification and cost estimates.

Solar & Renewables Live

Charge Controller Sizing Calculator

Size MPPT and PWM solar charge controllers per NEC 690.7. Cold-weather Voc correction, string configuration, and common controller size recommendations.