DC Wire Sizing Calculator — Gauge, Voltage Drop & NEC Ampacity
Size Copper and Aluminum Conductors for 12V, 24V, and 48V Solar, Battery, and DC Distribution Circuits
Free DC wire sizing calculator for solar installers, marine electricians, and off-grid system builders. Enter the circuit current, one-way wire run distance, and system voltage, and the calculator determines the minimum wire gauge (AWG) that satisfies both NEC ampacity requirements and your target voltage drop percentage. Supports copper and aluminum conductors, 12V through 48V systems, and all standard conduit fill and temperature correction factors per NEC Article 310. Displays actual voltage drop in volts and percent, power loss in watts, and the NEC ampacity table reference for the recommended conductor size.
Size the solar array feeding these DC circuits
Solar Array Sizing Calculator →Size the battery bank connected to your DC bus
Battery Bank Sizing Calculator →Select the charge controller for your system
Charge Controller Sizing Calculator →Check conduit fill for your DC runs
Conduit Fill Calculator →Read the complete DC wiring guide
DC Wiring Guide →How It Works
-
Enter Circuit Parameters
Input the maximum continuous current in amps and the system voltage (12V, 24V, 48V, or custom). For solar panel circuits, use the short-circuit current (Isc) multiplied by 1.25 per NEC 690.8. For battery circuits, use the maximum inverter draw current. For DC loads, use the rated current of the device.
-
Set Wire Run Distance
Enter the one-way distance from source to load in feet. The calculator automatically accounts for the round-trip (source to load and return) in the voltage drop calculation. Measure the actual wire route, not the straight-line distance. Include vertical runs, routing around obstacles, and service loops.
-
Select Conductor Material and Insulation
Choose copper or aluminum conductor. Select the insulation type (THHN/THWN-2, USE-2, PV Wire, etc.) which determines the temperature rating and NEC ampacity column. Solar installations typically require USE-2 or PV Wire for exposed outdoor runs and THWN-2 for conduit runs.
-
Set Voltage Drop Target
Enter your maximum acceptable voltage drop as a percentage. NEC recommends 3% for branch circuits and 5% total for feeder plus branch circuit combined. For solar and battery circuits, many designers target 2% or less to maximize energy transfer efficiency. Lower voltage systems require tighter voltage drop targets in absolute terms.
-
Review Wire Size Recommendation
The calculator displays the minimum AWG that satisfies both the voltage drop target and NEC ampacity requirements, whichever is more restrictive. It shows the actual voltage drop in volts and percentage, power lost as heat in the conductors, NEC ampacity at the selected temperature rating, and whether voltage drop or ampacity was the controlling factor.
Built For
- Solar installers sizing conductors from PV array to charge controller and charge controller to battery bank per NEC 690
- Marine electricians sizing battery cables and DC distribution wiring on boats per ABYC E-11 standards
- Off-grid system builders sizing the main DC bus wiring between battery bank, inverter, and charge controller
- RV electricians sizing shore-to-battery charging cables and 12V distribution circuits in motorhomes and trailers
- Automotive electricians sizing power cables for aftermarket accessories, winches, and auxiliary lighting on 12V and 24V systems
- Telecom technicians sizing DC power feeds from rectifiers to equipment racks in -48V telecom installations
Features & Capabilities
Dual-Constraint Sizing
Evaluates both NEC ampacity (current-carrying capacity based on insulation temperature rating, conduit fill, and ambient temperature) and voltage drop (based on conductor resistance, current, and distance). Reports which constraint is controlling and recommends the larger gauge that satisfies both. In low-voltage DC systems, voltage drop almost always governs.
Copper and Aluminum Support
Sizes conductors in both copper and aluminum with accurate resistivity values at operating temperature. Aluminum has 61% the conductivity of copper and requires a wire two sizes larger for the same ampacity. The calculator shows both options side by side so you can compare gauge, weight, and cost tradeoffs.
NEC Article 310 Ampacity Tables
References NEC Table 310.16 (formerly 310.15(B)(16)) for ampacity at 60C, 75C, and 90C insulation ratings. Applies ambient temperature correction factors per Table 310.15(B)(1) and conduit fill adjustment factors per Table 310.15(C)(1). These corrections reduce allowable ampacity in hot environments or crowded conduits.
Voltage Drop Visualization
Displays voltage at the source, voltage at the load after drop, and the percentage loss. For battery charging circuits, shows how voltage drop reduces the effective charging voltage reaching the battery terminals. A 0.5V drop on a 48V circuit is negligible, but 0.5V on a 12V circuit can prevent a battery from reaching full charge.
Power Loss Calculation
Calculates the power dissipated as heat in the conductors (I2R losses). On high-current DC circuits, power loss can be substantial. A 100A circuit on 50 feet of 2 AWG copper loses approximately 65W as heat. This wasted energy reduces system efficiency and heats conduits. Upsizing the conductor by one gauge cuts the loss roughly in half.
Solar-Specific NEC Factors
Automatically applies NEC 690.8 continuous-duty 125% current multiplier for PV source and output circuits. Applies NEC 690.7 cold-temperature voltage correction to string Voc for conductor insulation voltage rating verification. These NEC-specific solar requirements are frequently missed by general-purpose wire sizing tools.
Frequently Asked Questions
Learn More
DC Wiring Best Practices for Solar Systems
DC wiring guide for solar installations. Covers voltage drop calculations, wire sizing, connectors, conduit, grounding, NEC 690 overcurrent protection, rapid shutdown, and labeling requirements.
Related Tools
Solar Array Sizing Calculator
Size your solar panel array from daily kWh load, peak sun hours by region, system losses, and tilt derating. Grid-tied and off-grid modes with monthly production estimates.
Battery Bank Sizing Calculator
Size lead-acid or LiFePO4 battery banks for off-grid and backup solar systems. Accounts for depth of discharge, days of autonomy, temperature derating, and battery configuration.
Charge Controller Sizing Calculator
Size MPPT and PWM solar charge controllers per NEC 690.7. Cold-weather Voc correction, string configuration, and common controller size recommendations.