Motor Starting Voltage Drop Calculator
LRA from Code Letter, Transformer Impedance, Cable Impedance, and Risk-Tiered Results for Industrial Power Systems
Free motor starting voltage drop calculator for electrical engineers, plant electricians, and power system designers who need to verify that a motor start will not cause excessive voltage dip. Enter the motor horsepower, NEMA code letter, transformer kVA and impedance, and cable length and size, and the calculator returns the expected voltage drop at the motor terminals during locked-rotor inrush. Results are classified into risk tiers: OK (under 5%), CAUTION (5-10%), HIGH (10-15%), and FAIL (over 15%) to help you assess whether the start is acceptable.
Large motor starts are one of the most common causes of nuisance trips, PLC faults, and flickering lights in industrial facilities. A 200 HP motor on a 1000 kVA transformer can pull 6-7 times its full load current during starting, and if the transformer impedance and cable impedance are high enough, the voltage can sag below the threshold where contactors drop out or VFDs fault. This calculator models the transformer impedance plus cable impedance against the motor locked-rotor inrush, giving you a conservative screening estimate before you energize the motor for the first time.
The calculator shows the voltage at the motor terminals after both transformer and cable drop, which is critical for motors with high-inertia loads that need sufficient torque during acceleration. If the terminal voltage drops below about 80% of rated, the motor may stall because torque drops as the square of voltage.
Size transformers for motor loads and demand factors
Transformer Sizing Calculator →Check conduit fill with motor feeder conductors
Conduit Fill Calculator →Understand motor starting voltage drop analysis methods
Motor Starting Voltage Drop Guide →How It Works
-
Enter Motor Data
Input the motor horsepower, voltage rating (single-phase or three-phase), and NEMA code letter. The calculator uses the code letter to determine the locked-rotor kVA per HP and computes the locked-rotor amps (LRA) per NEC Table 430.7(B).
-
Enter Transformer Data
Input the transformer kVA rating and impedance percentage. The transformer impedance is the dominant factor in most motor starting voltage drop calculations. The calculator assumes an infinite bus on the primary side.
-
Enter Cable Data
Input the cable size (AWG or kcmil), length in feet, and conduit material (steel or PVC). The calculator uses NEC Chapter 9 Table 9 impedance values to compute the cable voltage drop contribution.
-
Review Risk Tier and Recommendations
Check the terminal voltage, voltage drop percentage, and the assigned risk tier. If the result is CAUTION or worse, the calculator suggests mitigation options such as reduced-voltage starting, larger cable, or a dedicated transformer.
Built For
- Electrical engineers checking whether a new 150 HP compressor motor will cause bus voltage to sag below acceptable limits on an existing 750 kVA transformer
- Plant electricians troubleshooting why a large motor start trips the MCC contactors or causes PLC faults on adjacent equipment
- Power system designers selecting transformer size and cable gauge to support a new motor installation with acceptable voltage drop
- Consulting engineers preparing a motor starting study for a permit application or equipment procurement specification
Features & Capabilities
Transformer + Cable Impedance Model
Models the voltage drop through the transformer impedance and cable impedance during locked-rotor inrush. Calculates the motor terminal voltage and percentage drop with the sqrt(3) factor for three-phase systems.
NEMA Code Letter LRA Lookup
Automatically determines locked-rotor amps from the motor horsepower and NEMA code letter per MG-1 Table 10-1. Covers code letters A through V for standard induction motors.
Risk-Tiered Results
Classifies the voltage drop into four tiers: OK (under 5%), CAUTION (5-10%), HIGH (10-15%), and FAIL (over 15%). Each tier includes practical guidance on whether the start is acceptable or what mitigation to consider.
Cable Impedance from NEC Tables
Uses NEC Chapter 9 Table 9 resistance and reactance values for common conductor sizes in steel and PVC conduit. Accounts for both resistive and reactive components of cable impedance.
Assumptions
- Motor locked-rotor current is derived from the NEC code letter kVA/HP range, assuming a standard NEMA Design B induction motor.
- Cable impedance values are based on NEC Chapter 9 Table 9 for 60 Hz, 75 C conductor temperature.
- The utility source is assumed to be an infinite bus at the transformer primary. Utility source impedance is not modeled.
Limitations
- Does not model the transient voltage recovery profile during motor acceleration, only the initial locked-rotor voltage dip.
- Does not account for voltage support from power factor correction capacitors, other running motors, or generator excitation response.
- Assumes a single motor starting on a radial system. Multiple motors starting simultaneously or motors on networked buses require a full power system study.
References
- IEEE 141-1993 (Red Book) - Recommended Practice for Electric Power Distribution for Industrial Plants, Chapter 8: Motor Starting.
- NEMA MG-1 - Motors and Generators, Table 10-1: Locked-Rotor kVA per Horsepower by Code Letter.
- NEC Chapter 9 Table 9 - AC Resistance and Reactance for 600 V Cables in Conduit.
Frequently Asked Questions
Learn More
Motor Starting Voltage Drop Analysis
How to calculate voltage drop during motor starting per IEEE 141, including locked rotor current from NEC code letters, transformer impedance modeling, and cable sizing.
Related Tools
Can I Run This On That?
Check if your circuit breaker and wiring can handle a specific appliance. Enter breaker size, wire gauge, and load wattage for a pass/fail verdict based on NEC standards.
Wire Sizing Calculator
Find the right AWG wire gauge for any electrical run. Enter amps, distance, and voltage to get NEC-compliant sizing with derating, voltage drop, and copper vs aluminum cost comparison.
Generator Sizing Calculator
What size generator do you need? Add your appliances and loads to calculate total running watts and starting surge. Get a recommended generator size with built-in headroom.