Skip to main content
Electrical Free Pro Features Available

Transformer Sizing Calculator - NEC Article 220 Demand Factor Load Analysis for Transformer Selection

Calculate transformer kVA rating using demand factors, load categories, and voltage configurations

Size dry-type and liquid-filled transformers using NEC Article 220 demand factor calculations. Enter connected loads by category (lighting, receptacles, HVAC, motors, kitchen equipment) and apply NEC demand factors to determine the calculated load in kVA. Supports single-phase and three-phase transformers with standard voltage configurations including 480-208/120V, 480-240/120V, 240-120V, and 600-208/120V. Includes motor load considerations per NEC 430, largest motor 125% rule, and continuous load 125% factor. Shows recommended standard transformer kVA sizes from 15 kVA through 2500 kVA.

Pro Tip: NEC demand factors are minimums for code compliance, not engineering recommendations. A transformer sized exactly at 100% of NEC calculated load will run hot and have zero capacity for future growth. Best practice is to size the transformer at 75-80% loading of its kVA rating, leaving 20-25% headroom. This keeps operating temperature lower (extending insulation life by roughly 50%), provides room for load growth, and maintains voltage regulation under peak demand. The cost difference between one standard kVA size is typically 10-15% - cheap insurance.

PREVIEW All Pro features are currently free for a limited time. No license key required.

Electrical Service & Transformer Sizing Calculator

How It Works

  1. Select Transformer Configuration

    Choose single-phase or three-phase, primary voltage, secondary voltage, and winding configuration (delta-wye, wye-wye, delta-delta). The most common commercial configuration is 480V delta primary to 208Y/120V secondary.

  2. Enter Connected Loads by Category

    Input loads in watts or VA for each NEC category: general lighting (per Table 220.12), general receptacles, fixed appliances, HVAC equipment, kitchen equipment, motors, and other loads. Each category has specific demand factors per NEC Article 220.

  3. Apply Demand Factors

    The calculator automatically applies NEC Article 220 demand factors: general lighting per Table 220.42, receptacle loads per 220.44, kitchen equipment per 220.56, and motor loads per 430.24 (125% of largest motor plus sum of the rest). Review each factor applied.

  4. Review Calculated Load

    See the total connected load, demand factor deductions, net calculated load in kVA, and the recommended standard transformer size. The calculator selects the next standard kVA rating above the calculated load and shows the resulting loading percentage.

  5. Evaluate Future Growth

    Add anticipated future loads to see if the selected transformer can accommodate growth without replacement. The calculator shows loading at current and projected loads, with warnings when projected loading exceeds 80% of transformer rating.

Built For

  • Electrical engineers sizing transformers for new commercial building construction projects
  • Electrical contractors selecting transformers for tenant improvement and renovation work
  • Facility managers evaluating whether existing transformers can handle additional equipment loads
  • Industrial electricians sizing step-down transformers for new motor control center installations
  • Utility coordinators determining pad-mount transformer sizes for new service installations
  • Data center designers calculating transformer requirements for IT power distribution units

Features & Capabilities

NEC Article 220 Demand Factors

Automatically applies NEC demand factors for general lighting (Table 220.42), receptacle loads (220.44), kitchen equipment (220.56), and laundry equipment. Handles the tiered demand structure where the first portion of load uses a higher factor.

Motor Load Handling

Applies NEC 430.24 requirements: 125% of the largest motor's full load amps plus 100% of all remaining motors. Converts motor HP to FLA using NEC Tables 430.248 and 430.250 for accurate kVA contribution.

Standard kVA Size Selection

Recommends the appropriate standard transformer kVA size from the standard series: 15, 25, 37.5, 45, 75, 112.5, 150, 225, 300, 500, 750, 1000, 1500, 2000, and 2500 kVA. Shows loading percentage at each candidate size.

Voltage Drop Estimation

Estimates secondary voltage drop at calculated loading based on typical transformer impedance values (3-6%). Flags configurations where voltage regulation may cause problems for sensitive equipment at the end of long secondary feeders.

Continuous Load Factor

Applies the NEC 125% continuous load factor for loads operating three hours or more. Properly categorizes lighting and HVAC as continuous while treating receptacles as non-continuous unless specified otherwise.

Frequently Asked Questions

NEC demand factors account for the statistical reality that not all connected loads operate simultaneously at full capacity. For example, NEC Table 220.42 allows general lighting demand at 100% for the first 10,000 VA, then 50% for the next 110,000 VA, then 25% for all load over 120,000 VA. Without demand factors, a 100,000 sq ft building would require a massively oversized transformer. Demand factors allow engineers to size transformers for realistic peak demand rather than theoretical maximum connected load.
NEC 430.24 requires that the largest motor in the group be calculated at 125% of its full-load amperage, with all remaining motors at 100%. Convert motor horsepower to full-load amps using NEC Table 430.248 (single-phase) or 430.250 (three-phase), then calculate the kVA contribution. Motor starting inrush (typically 6-8 times FLA) is a momentary load that transformers can handle without permanent damage but may cause voltage dip - consider this when sizing for sensitive loads.
Transformers are rated in kVA (kilovolt-amperes), which is apparent power and includes both real power (kW) and reactive power (kVAR). The relationship is kVA = kW / power factor. At unity power factor (1.0), kVA equals kW. Most commercial buildings have a power factor of 0.85-0.90, meaning a 100 kW load draws 111-118 kVA from the transformer. Always size the transformer in kVA, not kW, to account for reactive power drawn by motors, fluorescent lighting, and electronic equipment.
Transformer impedance (typically expressed as %Z) determines the voltage drop under load and the available fault current on the secondary. Standard dry-type transformers have impedances of 3-6%. A 5.75% impedance transformer will drop approximately 5.75% of rated voltage at full load and unity power factor. Lower impedance means better voltage regulation but higher available fault current. Higher impedance reduces fault current but increases voltage drop. Balance these competing factors based on the downstream equipment requirements.
Dry-type transformers are standard for indoor installations up to about 2500 kVA. They require no containment for dielectric fluid, have lower fire risk, and are easier to maintain. Liquid-filled (oil or silicone) transformers are more efficient, run cooler, and cost less per kVA for larger sizes. They are standard for outdoor pad-mount and utility installations. Indoor use of liquid-filled transformers requires a vault meeting NEC 450.26 unless the fluid is listed as less-flammable (silicone). Most commercial and industrial buildings use dry-type transformers inside and liquid-filled transformers outside.
Standard transformer ratings assume installation at or below 3,300 feet (1,000 meters) above sea level. At higher altitudes, the thinner air provides less cooling, requiring the transformer to be derated. The general guideline is to derate 0.3% per 330 feet (100 meters) above 3,300 feet for dry-type transformers. At 5,000 feet, a transformer must be derated approximately 1.5%. Alternatively, specify a transformer designed for high-altitude operation, which has enhanced cooling or a larger core to compensate for reduced air density.
NEC 215.2(A)(1) and 210.20(A) require that conductors and overcurrent devices be sized at 125% of the continuous load plus 100% of the non-continuous load. Continuous loads are those expected to operate for three hours or more, which includes most lighting, HVAC, and process loads. This 125% factor affects the transformer secondary overcurrent protection sizing and may influence the transformer kVA selection when the majority of loads are continuous. Some transformer manufacturers rate their units for 100% continuous loading when properly ventilated.
Disclaimer: This calculator provides transformer sizing estimates based on NEC Article 220 demand factors. Actual transformer selection must consider site-specific conditions including altitude, ambient temperature, harmonic loads, future growth, and utility requirements. Always consult a licensed electrical engineer for transformer specification. ToolGrit is not responsible for transformer sizing, electrical design, or code compliance outcomes.

Learn More

Electrical

How to Size a Transformer Using NEC Article 220

Step-by-step guide to transformer sizing using NEC Article 220 demand factors. Covers single-phase and three-phase service calculations with worked examples.

Related Tools

Electrical Live

Can I Run This On That?

Check if your circuit breaker and wiring can handle a specific appliance. Enter breaker size, wire gauge, and load wattage for a pass/fail verdict based on NEC standards.

Electrical Live

Wire Sizing Calculator

Find the right AWG wire gauge for any electrical run. Enter amps, distance, and voltage to get NEC-compliant sizing with derating, voltage drop, and copper vs aluminum cost comparison.

Electrical Live

Generator Sizing Calculator

What size generator do you need? Add your appliances and loads to calculate total running watts and starting surge. Get a recommended generator size with built-in headroom.