Backflow prevention devices protect the potable water supply from contamination caused by cross-connections. When pressure in a non-potable system exceeds the supply pressure (backpressure) or when supply pressure drops below atmospheric (backsiphonage), water can flow backward through a cross-connection and contaminate the drinking water supply.
This guide covers the selection of testable backflow prevention assemblies -- Reduced Pressure Zone (RPZ), Double Check Valve Assembly (DCVA), and Pressure Vacuum Breaker (PVB) -- per the AWWA Manual M14 (Backflow Prevention and Cross-Connection Control) and the USC Foundation for Cross-Connection Control standards. Sizing must balance flow capacity against the assembly's pressure loss to ensure adequate downstream pressure.
Hazard Classification and Assembly Selection
The type of backflow preventer required depends on the degree of hazard and whether the risk is from backpressure, backsiphonage, or both:
- High hazard (health hazard): Contaminants that could cause illness or death. Examples: chemical feed systems, sewage, medical gas systems, boiler water with chemical treatment, irrigation with injected chemicals. Requires RPZ assembly.
- Low hazard (non-health hazard): Pollutants that are aesthetically objectionable but not a health threat. Examples: HVAC makeup water without chemical treatment, food-grade processing, fire sprinkler systems (no antifreeze). Requires DCVA (backpressure and backsiphonage) or PVB (backsiphonage only).
Assembly types:
- RPZ (Reduced Pressure Zone): Two check valves with a relief valve between them that opens to atmosphere if both checks fail. Protects against both backpressure and backsiphonage. Required for all high-hazard applications. Must be installed in a location where the relief valve can discharge (not in a vault that could flood).
- DCVA (Double Check Valve Assembly): Two independently operating check valves in series. Protects against both backpressure and backsiphonage for low-hazard applications. Can be installed in vaults.
- PVB (Pressure Vacuum Breaker): A spring-loaded check valve with an air inlet. Protects against backsiphonage only. Must be installed 12 inches above the highest downstream point. Used for irrigation systems without backpressure.
Backflow Preventer Sizing Calculator
Size RPZ, DCVA, and PVB backflow prevention assemblies by flow rate and pressure loss. Covers cross-connection hazard levels per AWWA and local codes.
Sizing for Flow and Pressure Loss
Backflow preventers create significant pressure loss. Sizing must ensure adequate downstream pressure at peak demand flow. The pressure budget is:
Pdownstream = Psupply − ΔPmeter − ΔPbackflow − ΔPpiping − ΔPelevation
Where all terms are in psi. The downstream pressure must meet the requirements of the served equipment (typically 15–20 psi minimum for plumbing fixtures, 35–50 psi for irrigation).
Typical pressure losses at rated flow:
- RPZ assemblies: 10–15 psi at rated flow (varies by size and manufacturer)
- DCVA assemblies: 3–8 psi at rated flow
- PVB assemblies: 5–10 psi at rated flow
RPZ assemblies have the highest pressure loss because of the relief valve mechanism between the two checks. This pressure loss is the trade-off for the highest level of protection.
Critical sizing rule: Never select an assembly based on pipe size alone. A 2-inch assembly may be required on a 2-inch line, but the flow demand and available pressure must be verified. Oversizing is also a problem -- an assembly that rarely sees flow above 10% of its capacity can have sluggish check valves that do not seat properly.
Backflow Preventer Sizing Calculator
Size RPZ, DCVA, and PVB backflow prevention assemblies by flow rate and pressure loss. Covers cross-connection hazard levels per AWWA and local codes.
Installation and Access Requirements
Proper installation is critical for both function and testability:
RPZ assemblies:
- Must be installed 12 inches minimum above grade or floor (to allow relief valve discharge and prevent submersion)
- Must be in an accessible location for annual testing -- test cocks must be reachable
- Must have adequate drainage for relief valve discharge (RPZ can discharge at full flow rate if both checks fail simultaneously)
- Horizontal installation preferred. Some models are USC-approved for vertical installation.
DCVA assemblies:
- Can be installed in vaults, below grade, or in mechanical rooms
- Must be accessible for annual testing
- Horizontal or vertical installation per manufacturer approval
PVB assemblies:
- Must be installed 12 inches above the highest downstream point (the assembly must not be subjected to backpressure)
- Must be protected from freezing in cold climates
- Cannot be installed where continuous pressure is maintained downstream (this would subject the air inlet to backpressure)
All testable assemblies require isolation valves (gate or butterfly) upstream and downstream for testing and maintenance. Test cocks are integral to the assembly and must remain accessible.
Backflow Preventer Sizing Calculator
Size RPZ, DCVA, and PVB backflow prevention assemblies by flow rate and pressure loss. Covers cross-connection hazard levels per AWWA and local codes.
Annual Testing and Maintenance
Testable backflow prevention assemblies must be tested at installation and annually thereafter. Most jurisdictions require testing by a state-certified backflow prevention assembly tester. The test verifies that each component (check valves, relief valve, air inlet) operates within specified parameters.
RPZ test points:
- First check valve: must hold at least 1 psi differential
- Relief valve: must open before the zone pressure drops to within 2 psi of downstream pressure
- Second check valve: must be tight (no leakage)
DCVA test points:
- First check: must hold at least 1 psi differential
- Second check: must be tight (no leakage)
Common failure modes and maintenance:
- Fouled check valves: Debris, sediment, or mineral buildup prevents the check disc from seating. Solution: disassemble and clean or replace the check module.
- Relief valve weeping: On RPZ assemblies, a continuously weeping relief valve indicates that the first check is not maintaining adequate differential. The first check needs service.
- Rubber degradation: Check valve discs and O-rings degrade over time, especially in high-chlorine water or water with chemical contaminants. Replace rubber parts per manufacturer intervals (typically every 5–8 years).
Backflow Preventer Sizing Calculator
Size RPZ, DCVA, and PVB backflow prevention assemblies by flow rate and pressure loss. Covers cross-connection hazard levels per AWWA and local codes.
Backflow Preventer Sizing Calculator
Size RPZ, DCVA, and PVB backflow prevention assemblies by flow rate and pressure loss. Covers cross-connection hazard levels per AWWA and local codes.