Junction Box Fill Calculator: NEC Article 314.16 Box Volume
Count Conductors and Calculate Required Box Size per NEC Table 314.16(B)
Free NEC junction box fill calculator per Article 314.16. Enter the number of conductors by AWG size, cable clamps, support fittings, devices (switches/receptacles), and equipment grounding conductors to calculate the total volume required and minimum box size. Uses conductor volume allowances from NEC Table 314.16(B).
\nBox fill violations are one of the most common NEC inspection failures. Overfilled boxes cause wire damage, increase fire risk from heat buildup, and make devices difficult to install properly. This calculator counts every conductor and fitting per NEC rules and recommends the smallest compliant box.
Calculate conduit fill for wire pulls
Conduit Fill Calculator →Calculate conduit bending for offsets and saddles
Conduit Bending Calculator →Look up NEMA plug and receptacle configurations
NEMA Configuration Reference →Size wire gauge for your circuit
Wire Sizing Calculator →How It Works
-
Enter Conductor Count by Size
Count all conductors entering the box by AWG size (#14, #12, #10, #8, #6). Each conductor (hot, neutral, traveler) counts individually. Do not count pigtails that originate inside the box.
-
Count Cable Clamps
Count the number of cable clamps or connectors inside the box. All internal clamps together count as one conductor volume, regardless of how many clamps there are.
-
Count Devices
Count switches and receptacles. Each single yoke device (switch, receptacle) counts as two conductor volumes of the largest wire connected to it. A combination device on one yoke still counts as two.
-
Count Equipment Grounds
All equipment grounding conductors together count as one conductor volume of the largest ground wire present. If an equipment bonding jumper is present, add one more volume of the largest EGC.
-
Review Required Volume
The calculator sums all conductor volume allowances and shows the minimum box volume in cubic inches. It recommends standard box sizes that meet or exceed the requirement.
Built For
- Electricians selecting box sizes during rough-in to pass inspection on the first try
- Electrical inspectors verifying box fill compliance during inspection
- Apprentice electricians learning NEC box fill counting rules for journeyman exams
- Estimators determining correct box sizes for material takeoffs
- Electrical engineers specifying box sizes on construction drawings
- Maintenance electricians verifying existing box capacity before adding circuits
- Residential electricians sizing boxes for 3-way and 4-way switch configurations
Features & Capabilities
NEC Table 314.16(B) Volumes
Conductor volume allowances per NEC: #14 AWG = 2.0 cu. in., #12 = 2.25 cu. in., #10 = 2.5 cu. in., #8 = 3.0 cu. in., #6 = 5.0 cu. in.
Complete Counting Rules
Implements all NEC 314.16(B) counting rules: conductors, cable clamps (1 volume total), devices (2 volumes each), EGC (1 volume for all), equipment bonding jumpers.
Standard Box Recommendations
Shows standard box sizes (single-gang, double-gang, 4" square, 4-11/16" square, etc.) with volumes. Recommends the smallest box that meets the calculated requirement.
Multiple Wire Sizes
Handles mixed wire sizes in the same box. Uses the largest conductor size for clamp and device volume calculations per NEC rules.
Visual Volume Breakdown
Shows the volume contribution of each component (conductors, clamps, devices, grounds) so you can see what is using box capacity.
PDF Export
Export box fill calculations as a branded PDF for inspection documentation or submittal packages.
Frequently Asked Questions
Learn More
NEC 314.16 Box Fill: How to Count Conductors and Pass Inspection
NEC 314.16 box fill rules explained. How to count conductors, clamps, devices, and grounds for junction box cubic inch calculations.
Related Tools
Can I Run This On That?
Check if your circuit breaker and wiring can handle a specific appliance. Enter breaker size, wire gauge, and load wattage for a pass/fail verdict based on NEC standards.
Wire Sizing Calculator
Find the right AWG wire gauge for any electrical run. Enter amps, distance, and voltage to get NEC-compliant sizing with derating, voltage drop, and copper vs aluminum cost comparison.
Generator Sizing Calculator
What size generator do you need? Add your appliances and loads to calculate total running watts and starting surge. Get a recommended generator size with built-in headroom.