Motor FLA Lookup (NEC 430)
NEC table full-load amps with overload, breaker, fuse, and wire sizing per Article 430
Free motor full-load amperage lookup for electricians, panel designers, and maintenance planners who need NEC-compliant conductor and overcurrent protection sizing for motor circuits. Select motor horsepower, voltage, and phase (single or three-phase), and the calculator returns the NEC Table 430.248 (single-phase) or 430.250 (three-phase) full-load current. From that FLA, it calculates overload heater sizing per NEC 430.32 (115% or 125% of FLA based on service factor and temperature rise), short-circuit and ground-fault protection sizing per NEC 430.52 for inverse-time breakers, dual-element fuses, and instantaneous-trip breakers, and minimum conductor ampacity per NEC 430.22 (125% of FLA) with wire gauge from NEC Table 310.16 at 75°C. NEC 430.6(A)(1) requires using table FLA values, not nameplate amps, for conductor and overcurrent sizing. This distinction trips up apprentices and journeymen alike, and using nameplate current instead of table current is one of the most common code violations found during inspections of motor installations.
Calculate voltage, current, and power relationships
Ohm's Law / Power Wheel Calculator →Look up locked-rotor amps from NEC code letters
Motor Starting Current / Code Letter Calculator →Check cable tray fill for motor feeder cables
Cable Tray Fill Calculator (NEC 392) →How It Works
-
Select Motor Parameters
Choose the motor horsepower, voltage, and phase (single-phase or three-phase). For single-phase motors, the calculator uses NEC Table 430.248. For three-phase motors, it uses NEC Table 430.250. These tables cover standard NEMA motor voltages from 115V to 460V.
-
Review Full-Load Amperage
The calculator displays the NEC table FLA for the selected motor. This is the value required by NEC 430.6(A)(1) for sizing conductors and short-circuit protection. It is not the same as nameplate amps, which are used only for overload protection.
-
Review Protection and Wire Sizing
The output shows overload heater sizing (115% or 125% of FLA), maximum breaker and fuse sizes per NEC 430.52, and minimum conductor ampacity with the corresponding wire gauge from NEC Table 310.16 at 75°C terminal rating. Adjust for ambient temperature and conduit fill as needed.
Assumptions
- Motor is a standard squirrel-cage induction type at standard NEMA voltages.
- NEC table FLA values are from the current edition of NFPA 70 Tables 430.248 and 430.250.
- Wire sizing is based on NEC Table 310.16 at 75°C in a raceway with no more than three current-carrying conductors.
- Overload sizing assumes a service factor of 1.15 or greater (125% multiplier). Motors with SF less than 1.15 require 115%.
Limitations
- Does not cover wound-rotor, synchronous, or DC motor sizing.
- Does not apply ampacity correction for ambient temperatures above 30°C or conduit fill above three conductors.
- Does not calculate feeder sizing for multiple motors on a common feeder (NEC 430.24).
- Does not account for voltage drop over long conductor runs.
References
- NEC (NFPA 70) Table 430.248 - Full-Load Currents, Single-Phase AC Motors
- NEC (NFPA 70) Table 430.250 - Full-Load Currents, Three-Phase AC Motors
- NEC (NFPA 70) Table 430.52 - Maximum Rating or Setting of Motor Branch-Circuit Short-Circuit and Ground-Fault Protective Devices
- NEC (NFPA 70) Table 310.16 - Conductor Ampacities at 60°C, 75°C, and 90°C
- NEC 430.6(A)(1) - Ampacity and Motor Rating Determination
- NEC 430.22 - Single Motor Branch-Circuit Conductor Size
- NEC 430.32 - Continuous-Duty Motors Overload Protection
Frequently Asked Questions
Learn More
Ohm's Law, Watt's Law, and the AC Power Triangle
The 12 Ohm's Law and Watt's Law relationships explained for DC and AC circuits. Power factor, real vs apparent vs reactive power, and worked motor load examples.
Motor Circuit Design with NEC Article 430
Complete motor circuit design from FLA lookup through wire sizing, overload selection, and branch circuit protection per NEC 430. Worked 25 HP example.
Cable Tray Fill and Installation per NEC 392
Cable tray types, fill rules, single-conductor vs multiconductor differences, ampacity derating, and separation requirements per NEC Article 392.
Motor Starting Methods and Code Letter Interpretation
What motor code letters mean, why starting current matters, and how to choose between DOL, wye-delta, soft starters, and VFDs.
Fault Current Analysis for Electrical Distribution
Why fault current matters, the point-to-point method, transformer impedance effects, AIC ratings, and the connection between fault current and arc flash.
Torque, Horsepower, and Power Transmission Fundamentals
The HP formula and where 5252 comes from. Torque vs speed, drivetrain efficiency, gearbox selection, motor speeds, and VFD vs gearbox decisions.
Related Tools
Can I Run This On That?
Check if your circuit breaker and wiring can handle a specific appliance. Enter breaker size, wire gauge, and load wattage for a pass/fail verdict based on NEC standards.
Wire Sizing Calculator
Find the right AWG wire gauge for any electrical run. Enter amps, distance, and voltage to get NEC-compliant sizing with derating, voltage drop, and copper vs aluminum cost comparison.
Generator Sizing Calculator
What size generator do you need? Add your appliances and loads to calculate total running watts and starting surge. Get a recommended generator size with built-in headroom.